• Online only
Earth Neutral Bridge Box for AC Protection Box

Product pictures for illustrative purposes only.

  • Earth Neutral Bridge Box for AC Protection Box

Earth Neutral Bridge Box Single Phase 25A

R1,100.00 including VAT

Accepted payment methods including Visa, Mastercard, SnapScan, and EFT

Order must be placed on this page to qualify for 2% EFT discount.


Earth Neutral Bridge Box

Quantity

Delivery & Returns

  • Delivery: Nationwide courier, 2–4 working days (main centres).
  • Oulying Areas: Delivery may be up to 7 days.
  • Returns: 7-day inspection period from date of delivery.
  • Pricing: All prices include VAT. Delivery calculated at checkout.
First time shopping with us? Here’s why you can trust Solar Shop. In Stock
1 Item

IMPORTANT

The products we sell must be installed by a qualified electrician/technician and must adhere to local wiring regulations and standards. We are not liable for any damages or warranty rejections as a result of incorrectly installed products or systems.

Earth Neutral Bridge Box

  • Essential component needed for the safe operation of backup and Hybrid solar systems
  • Function is replacing Earth Neutral bridge when system is in backup mode
  • Makes the Earth Leakage operate correctly on the output of the inverter during backup operation
  • Compatible with Sunsynk 5kW inverters

The Earth Neutral Bridge Box is an essential component for the safe operation of back up and hybrid solar systems up to 5kWAC Back up port power rating

The function of this product is to replace the earth neutral bridge that is exists when normal power is supplied from the utility.

The ACDB-ARENB-25A automatically creates a temporary earth/neutral bridge when inverter goes to back up mode due to loss of grid, thus avoiding the forming of earth ground loops.

Once the backup or hybrid inverter goes into back up mode and disconnects from the utility the existing bridge is lost. This has two side effects that require attention:

1. When a measurement is taken between the Earth and Neutral Conductor on the backup output circuit and elevated neutral voltage is measured.
2. With the Earth/Neutral bridge, any earth leakage device connected in the output circuit does not function correctly It is essential this ACDB-ARENB-25A is installed between the inverter backup out and the output distribution DB

ACDB-ARENB-25A
1 Item

Specific References

MPN
ACDB-ARENB-25A
New

Questions

Be the first to ask a question about this product!

Question about the product

* Required fields
(read)